Bizator  /  Adverts  /  equipment and materials  /  industrial equipment  /  generating machinery

Electronic discrete output module Siemens 6ES7132-4BD32-0AA0

Offer type: salePublished: 28.02.2015
Price:1 600 UAH
Company:ChP Gorlach
Seller:Vladimir Vladimirovich
Phones:
Show phone
Write a message
Address:Kyiv, Ukraine
Siemens 6ES7132-4BD32-0AA0 - electronic discrete output module for ET 200S, 4 DO Standard, 24 V DC / 2 A, of a width of 15 mm, pack of 5 pieces.

Manufacturer series - Siemens 6ES7132-4BD32-0AA0
Name of product - Electronic module Siemens Simatic DP
The voltage at the load L+ - 24 V DC from the power supply module (nominal)
Protection against reverse voltage - Yes (when using the same voltage as on the power module)
The reverse polarity protection Yes
Input current from load L+ (without load) - 10 mA per channel (max)
Input current from the internal bus to 3.3 VDC - 10 mA (max)
The power loss is 1.6 watts
Address space per module (with packaging without packaging) - 4 bits / 1 byte
Number of digital outputs - 4
The short circuit protection - Yes, for each channel
The threshold (type) of 2.8 to 7.2 And
The inductive limit trip voltage (L+) -55 / - 60 In
Lamp load is 10 watts (max)
Control digital input - Yes
Range load resistance - 12 - 3.400 Ohm
Output voltage
For signal "1" (min) - L+ (-1,0)
Output current for signal "1" (valid range from 0 to 60) - minutes 7 mA (rated 2)
Output current for signal "1" (valid range) - max 2.0 a (0 to 60 C)
For signal "0" (residual current) - 0.5 mA (max)
The delay of the output with a resistive load of 1 to "0" (max) - 50 µs (45 MS; typical value)
From 1 to "0" (max) - 120 µs (90 MS; typical value)
Parallel connection of 2 outputs for increased power No
For back-up control load Yes, per module
Switching frequency with resistive load - 1,000 Hz (max)
Switching frequency with inductive load - 2 Hz (max) at 0.5 N
On lamp - 10 Hz (max)
Total current of outputs (per group), mounting position up to 60 max - 4 And
Total current of outputs (per group), mounting position up to 40 max(vertical installation) - 4 And
Length of shielded cable (max) - 1.000 m
Length unshielded cable (max) - 600 m
Isochronous operation (application synchronized to the terminal) - Yes
Diagnostics functions are Not
The status indicator digital output - Yes, LED - green
Remark (parameter) - 1 byte
Galvanic isolation digital outputs between the channels - No
Galvanic isolation between channels and backplane - Yes
Isolation Tested voltage 500 V DC
Dimensions (W x h x D) 15 x 81 x 52 mm
Weight (kg) - 0,40